Due to electromagnetic induction, the metal shielding layer (or metal sheath) of long-line high-voltage single-core power cable generates induced voltage, leading to insulation aging, and reducing the insulation grade, resulting in reduced cable life; Once the induced voltage exceeds the sheath breakdown voltage value, the outer sheath is broken down, forming a single-core cable multi-point grounding fault. Therefore, the power industry standard DL/T401 "Guidelines for the selection of High-voltage Power cables" stipulates that a cable sheath protector must be used to limit the induced voltage and fault overvoltage on the metal shield (or metal sheath) of the power cable.
Technical parameter
| Model number |
System rated voltage kVr.m.s |
Power frequency withstand voltage/time kVr.m.s/s |
Residual voltage under 10kA lightning impulse current ≤kVp |
Dc U1mA reference voltage >kV |
2ms square wave flow capacity A |
L |
The leakage current at 0.75U1mA ≤ μA |
Models currently circulating on the market that are not marked according to the national bank standard JB/T8459 |
| LHQ-6 | 6 | 1.9/4 | 4.6 | 2.1 | 400 | 80 | 50 |
BHQ、BYL、 FBY、SHQ、 BYLS、 TBP-D |
| LHQ-10 | 10 | 3.6/4 | 8.7 | 4.0 | 400 | 107 | 50 | |
| LHQ-35 | 35 | 5/4 | 12 | 5.5 | 400 | 134 | 50 | |
| LHQ-110(Ⅰ) | 110 | 5.3/4 | 12 | 5.8 | 400 | 188 | 50 | |
| LHQ-110(Ⅱ) | 110 | 10/4 | 25 | 11.0 | 400 | 188 | 50 | |
| LHQ-220(Ⅰ) | 220 | 6/4 | 15 | 6.5 | 400 | 188 | 50 | |
| LHQ-220(Ⅱ) | 220 | 13.6/4 | 31 | 15.0 | 400 | 188 | 50 | |
| LHQ-500 | 500 | 7.5/4 | 18 * | 8.3Ãr | 400 | 134 | 50 |