Yemen Standard Glass Electrical Insulator
Category:
Product Description
Glass insulator ( glass electrical insulator, high voltage glass insulator, glass power line insulators) is a device primarily used in electrical and telecommunication systems to support and separate electrical conductors from their surrounding environment. it is typically made from glass materials that have high resistance to electrical current, allowing them to prevent the flow of electricity between conductors and the structures they are mounted on. the main purpose of a glass suspension insulators is to maintain the integrity and safety of electrical and telecommunication lines. by providing a barrier between the conductors and the structures (such as utility poles or towers),

| CATALOG No | UG40B110/200N | G70B146/320N |
UG100B1271320N UG100B146/320N |
G120B127/320N G120B146/320N |
UG160B146/400N UG160B155/400N UG160B170/400N |
| Figure No | QH-01-01 | QH-02-01 | QH-03-01 | QH-04-01 | QH-05-01 |
| Min.Mechanical failing load (KN) | 40 | 70 | 100 | 120 | 160 |
| Nominal diameter D(mm) | 178 | 255 | 255 | 255 | 280 |
| Nominal spacing P(mm) | 110 | 146 | 127/146 | 127/146 | 146/155/170 |
| Nominal creepage distance(mm) | 200 | 320 | 320 | 320 | 400 |
| Standard coupling | 11 | 16 | 16 | 16 | 20 |
| Dry lightning impulse withstand voltage(KV) | 50 | 100 | 100 | 100 | 110 |
| Wet power frequency withstand voltage(KV) | 25 | 40 | 40 | 40 | 45 |
| Power frequency puncture voltage(KV) | 90 | 130 | 130 | 130 | 130 |
| Radio interference voltage (μ V) 10kV 1MHz | 50 | 50 | 50 | 50 | 50 |
| Corona visual test P/C(KV) | 18/22 | 18/22 | 18/22 | 18/22 | 18/22 |

| CATALOG No | UG210B170/400N | UG240B170/400N | UG300B195/485N |
UG400B205/550N UG420B205/550N |
UG530B240/635N UG550B240/635N |
| Figure No | QH-06-01 | QH-07-01 | QH-08-01 | QH-08-01 | QH-09-01 |
| Min.Mechanical failing load (KN) | 210 | 240 | 300 | 400/420 | 530/550 |
| Nominal diameter D(mm) | 280 | 280 | 320 | 360 | 380 |
| Nominal spacing P(mm) | 170 | 170 | 195 | 205 | 240 |
| Nominal creepage distance(mm) | 400 | 400 | 485 | 550 | 635 |
| Standard coupling | 20 | 20/24 | 24 | 28 | 32 |
| Dry lightning impulse withstand voltage(KV) | 110 | 110 | 130 | 140 | 140 |
| Wet power frequency withstand voltage(KV) | 45 | 45 | 50 | 55 | 55 |
| Power frequency puncture voltage(KV) | 130 | 130 | 130 | 140 | 140 |
| Radio interference voltage (μ V) 10kV 1MHz | 50 | 50 | 50 | 50 | 50 |
| Corona visual test P/C(KV) | 18/22 | 18/22 | 18/22 | 18/22 | 18/22 |