Honduras Composite insulator

Insulator intended to connect it to a supporting.the top clamp for the conductor to be used for the transmission line are madeof aluminium alloy.

Product Description

The 220kv post type horizontal insulators consisting of a load-bearing cylindrical insulating solid core, a housing and end fitings attached to theinsulating core. it is intended to be subjected to cantilever, tensile and compressive loads.eed-fittings are made of ductile iron, and al ferrous parts, except stainless steel and aluminium shal be galvanized, and integral component orformed part of an insulator intended to connect it to a supporting.the top clamp for the conductor to be used for the transmission line are madeof aluminium alloy.

Core rod diameter mm 63
Minimum creepage Line mm 2655
Specified Cantilever Load(SCL) kN 13
Max. Designed Cantilever Load(MDCL) kN 6.5
Power frequency withstand voltage, dry kV 230
Power frequency flashover voltage, dry kV 280
Power frequency withstand voltage, wet kV 210
Power frequency flashover voltage, wet kV 250
Lightning impulse withstand voltage, positive kV 550
Lightning impulse falshover voltage, positive kV 600
Lightning impulse withstand voltage,negative kV 580
Lightning impulse falshover voltage,negative kV 620
Maximum RIV at 1M Hz dB 40
Minimum dry arcing distance mm 1050